Almost every watt an ASIC miner draws turns into heat. How you remove that heat affects noise, efficiency, how many machines fit in your space and how much infrastructure you need to build. There are three main approaches: air cooling, hydro (water) cooling and immersion cooling. This guide explains how each works, the trade-offs and which setups suit which buyers.
The three cooling methods at a glance
| Air | Hydro | Immersion | |
|---|---|---|---|
| How heat leaves | Fans push air across heatsinks | Coolant flows through cold plates on the hashboards | Whole miner submerged in dielectric fluid |
| Noise at the machine | Very loud | Low (pumps and dry coolers make some noise) | Low (pumps and dry coolers make some noise) |
| Density | Lowest | High | High |
| Infrastructure | Ventilation and exhaust | Pumps, piping, heat exchanger or dry cooler | Tanks, fluid, pumps, heat exchanger |
| Upfront complexity | Low | Medium to high | High |
| Dust exposure | High | Low | None |
| Heat reuse potential | Limited (warm air) | Good (warm water) | Good (warm fluid via exchanger) |
Air-cooled miners
Air cooling is the default. Most popular models, including the Antminer S21 XP and Whatsminer M60S, are air-cooled. Fans pull cool air through the front, across aluminium heatsinks bonded to the chips, and blow hot air out the back.
Advantages
- Plug-and-play: no plumbing or special fluids
- Easy to buy, sell and ship
- Simple to repair and widely understood
- The lowest upfront cost per unit of infrastructure
Drawbacks
- Loud, often 75 dB or more per machine
- Performance depends on intake air temperature
- Dust builds up and needs regular cleaning
- Needs a lot of airflow, so density is limited
Air cooling suits garages, outbuildings, containers with strong extraction and conventional hosting sites.
Hydro-cooled miners
Hydro miners are built for liquid cooling from the factory. Water or a water-glycol mix flows through cold plates attached to the hashboards and carries heat out to a dry cooler, cooling tower or heat exchanger. Examples include the Antminer S21 Hydro and S21 XP Hydro, and MicroBT’s hydro Whatsminer models.
Advantages
- Very high hashrate per unit. The S21 XP Hydro is rated at 473 TH/s at around 12 J/TH.
- Quiet at the machine, since there are no high-speed fans
- Stable chip temperatures, which helps efficiency and longevity
- Warm water is easy to reuse for heating buildings, greenhouses or water
Drawbacks
- Requires a complete liquid loop: pumps, piping, manifolds and a heat rejection unit
- Leaks and water quality must be managed carefully
- Higher power per unit, often 5 kW or more, so electrical planning is important
Hydro suits purpose-built sites, containers designed for liquid cooling and operators who want heat reuse. See our cooling and infrastructure range for dry coolers, hydro containers and related equipment.
Immersion cooling
In immersion setups, standard air-cooled miners are submerged in a tank of non-conductive (dielectric) fluid. Fans are removed, and the fluid absorbs heat directly from every component. Pumps circulate the fluid through a heat exchanger.
Advantages
- Excellent thermal stability and no dust at all
- Very quiet at the tank
- Allows conservative overclocking on some models, though it raises power draw and worsens J/TH
- Works with many standard air-cooled models
Drawbacks
- The highest upfront complexity: tanks, fluid, pumps, filters and heat exchangers
- Fluid is costly and maintenance is messy
- Fans must be removed and fan errors bypassed in firmware
- Converting machines may affect warranty terms, so check before you start
Immersion suits operators who already understand the technology or who need to run in hot, dusty environments.
How cooling affects efficiency
Cooler chips generally run more efficiently. Hydro and immersion keep chip temperatures steady regardless of the weather, which can help a machine hold its rated J/TH. Air-cooled miners in very hot climates may throttle, reducing hashrate.
Remember to count the cooling system’s own power, however. Pumps, dry cooler fans and extraction fans all draw electricity. Include that overhead when comparing setups.
Choosing the right cooling
- One to a few machines, garage or shed: air-cooled, with good intake and exhaust.
- Noise-sensitive location with a solid budget: hydro, or air-cooled with a proper silencer enclosure.
- Container or larger site: air-cooled containers are simplest; hydro containers maximise density.
- Hot, dusty climate: hydro or immersion protect hardware from heat and dust.
- Heat reuse: hydro is the most practical route to useful warm water.
Maintenance compared
Each cooling method has its own routine. Air-cooled miners need regular cleaning with compressed air, periodic fan replacement and intake filters changed before they clog. Hydro systems need coolant quality checks, leak inspections and occasional pump and filter servicing, but the miners themselves stay clean. Immersion tanks need fluid level and quality monitoring, filter changes and careful handling whenever a machine is lifted out for repair, which can be messy.
Think about who will do this work and how often. A setup that is simple to maintain is often more reliable in practice than a more advanced system that nobody has time to look after.
Upgrading later
Air-cooled hardware is the easiest to resell or move. Hydro miners need a buyer with a compatible loop. Immersion-converted machines may need their fans refitted before resale. Factor that flexibility into your decision.
Whichever route you take, size the cooling for your hottest month, not your average one. Undersized cooling is the most common reason miners throttle.
Explore cooling options
Compare air and hydro miners in the SHA-256 collection, then browse our cooling and infrastructure products for racks, hydro systems and containers. Not sure what your site needs? Contact us and describe your space and power.
Questions
Is hydro cooling more efficient than air cooling?
Hydro-specific miners often have better published efficiency, for example the S21 XP Hydro at around 12 J/TH. Remember to include the power used by pumps and dry coolers when comparing.
Can I put an air-cooled miner into immersion?
Many air-cooled models can be immersed after removing the fans and adjusting firmware to ignore fan errors. Check warranty terms first, as modifications may affect coverage.
Which cooling method is quietest?
Hydro and immersion are quiet at the machine. Their pumps and dry coolers still make some noise, but usually far less than air-cooled miners.
Do hydro miners need special power?
Hydro models often draw 5 kW or more per unit, so they need appropriately rated circuits and PDUs. Plan electrical work alongside the cooling loop.



